RPC with or without Ethernet
27
The default ID is the unit’s number, in this case RPC17DE-30
Change Alarm Threshold
The Current Alarm Threshold allows the user to set the current level for the internal alarm to sound.
This setting is only available on units with current monitoring circuitry.
Select “Change Alarm Threshold.” from the configuration menu, The RPC will display the following:
Type ‘N’ to keep the current value or type ‘Y’ to change the value and enter the new value, followed
by <cr> and the RPC will display next outlet group.
Default setting is approximately 80% of unit’s maximum current.
Current Unit ID: RPC17DE-30
Modify (Y/N)? y
Enter New Unit ID: Cab7_Rack1 RPC17DE-30
Outlet 1-4 buzzer alarm value : 1.0 Amps
Modify (Y/N)? y
Enter: 2.0
Outlet 5-8 buzzer alarm value : 7.0 Amps
Modify (Y/N)? n